Product introduction
GGD type AC low-voltage distribution cabinet is suitable for the power consumers of the power plant,the transformer substation,the industrial enterprises,etc whose electrical distribution system with AC 50Hz,380Vrated working voltage and 3150A rated working current,andit is used as the electric power conversion,distribution and control for the power equipment,the lighting equipment and the power distribution equipment.
GGD type AC low-voltage distributioncabinet is a new low-voltagedistribution cabinetdesigned by the principle of safe,economic,reasonable and reliable,and also according to the requirementsof the supervisor of energy dapartment,the general electric power users and thedesign department.This product has the advantages of high breaking capacity,good dynamic thermal stability,flexible electric schemes,convenient combination,strong series &practicability,novel structure,high degree of protectionect.So it can be used as updated productsof the low-voltage switchgear equipment.
GGD type AC low-voltage distribution cabinet conforms to the standards of,(Low-voltage switchgear and controlgear assemblies》IEC61439-17,《Low-voltage switchgear and controlgear assemblies>GB7251.1,etc
Ordering information
Please provide the following parameters when ordering:
1.Full product model (including main circuit project number and auxiliary electrical project number); 2.Main circuitry combination sequence diagram;
3.Electrical schematic diagram of auxiliary circuit;
4.Cabinet components list;
5.Other special requirements that do not conform to the normal use conditions of the product.
Technical parameters
型号 Type | 额定电压 Noninal voltag (V) | 额定电流 Rated current(A) | 额定短路开断电流 Rated short circuit switching current(KA) | 额定短路耐受电流 Short-circuit withstand current (KA) | 额定峰值耐受电流 Rated peak tolerance current(KA) | 外壳防护等级 Shell protection grade | |
GGD1 | 380 | A | 1000 | 15 | 15 | 30 | |
B | 600(630) | ||||||
C | 400 | ||||||
GGD2 | 380 | A | 1500(1600) | 30 | 30 | 63 | IP30 |
B | 1000 | ||||||
C | |||||||
GGD3 | 380 | A | 3150 | 50 | 50 | 105 | |
8 | 2500 | ||||||
C | 2000 |
Conditions of use
1.The ambient airtemperature is not higher than 40℃and not lower than-5℃,The average temperature is not higher than 35℃ within 24 hours.
2.For indoor installation,the altitude ofthe used site shall not exceed 2000m.
3.The ambient RH shall not exceed 50%at a maximum temperature of 40℃,allowing for higher relative humidity at lower temperature.
4.The inclination of the equipment with the vertical plane is not more than 5%when it is installed.
5.The equipment shall be installed in the working situation without violent vibration and striking,as well as a place where electrical components are corroded.
6.Customers may negotiate with the manufacturer for special requirements.
Installation and use
After arriving at the receiving place,the product should first check whether the package is intact.If the problem is found,the relevant departments should be informed in time to find out the cause,and the products that are not installed immediately should be stored in an appropriate place according to the normal conditions of use.
Product installation
The installation of the productshall be carried out according to the installation schematic,and the base channel steel and bolts shall be provided by the user.When the main busbar is installed,the lap surface should be repaired and leveled,treated clean,coated with neutral vaseline or taken other measures,and then fastened with bolts.
After installing,the product should be inspected and tested before operation:
1.Check whether the cabinet topcoat has fallen off,whether the cabinet is dry and clean.
2.Whether the operating mechanism of electrical components is flexible,there should be no jam or excessive operating force phenomenon.
3.Whether the variation ratio and polarity of instrument indication and transformer are accurate.
4.Whether the auxiliary contacts meet the requirements,whether the fuse core specification is correct,whether the setting value of the relay meets the design requirements,and whether the action is accurate.
5.Whether the contacts of the circuit meet the requirements of the electrical schematic.
6.Whether the protection circuit system meets the requirements.
7.The insulation resistance shall not be less than 1megohm with a 500V.