Product introduction
Type SC(B)series epoxy resin cast dry-type transformers,can be used as the upgrading of products of oil immersed distribution transformers,all kinds of dry-type transformers in the best performance products,especially for urban power grids,high-rise buildings,businesscenters,theaters,hospitals,hotels,tunnels,subway stations,wharves, airports,underground power station,laboratory,combined and otherimportant place.
Product features
Our company products the SC(B)series power transformersfor domestic early coil around the injection licensed product model certificate of low-noise low-loss resin dry-type transformers.Due to the advanced design,quality materials,scientific formulas,rigorous process and high standards of testing,the product has the following characteristics:
1.The high voltage winding of copper wire,low voltage winding woundof copper wire or copper foi,glass fiber mat is filled with wrapping,vacuum packing of the epoxy used without casting,curing to form a solid cylindrical overall,mechanical high strength,partial discharge of small,high reliability.
2.Antiflaming,anti-explosion will not pollute the environment.Glass fibre Coil winding coil such with self-extinguishing properties,and will ot produce electric arc for short-circuit,does not producetoxic or harmful gases in high temperature condition.
3.The coil does not absorb moisture,core clamps have a special corrosion protection layer,100%relative humidity and other harsh environment.Interrupt driving need not remove tide treatment.
4.Short circuit resistant and high level of lightning impulse.
5.The resin inside and outside the coil is thin,heat dispersion is good.Cooling air is used air cool in nature(AN).For any degree of protection transformer,equip with air-cooled system(AF),in order to improve overload capacity of short-term,and ensure safe operation.
6.Lower consumption,energy-saving.Running for a savings,can be maintenance-free
7.Small volume,light weight,small area,lower installation costs,not need to consider oil tank,fire protection and backup power,stand-by UPS.
8.Because there was no fire and explosion danger,installed in the load center can be distributed and fully close to the power point,thus reducing the line low cost and save the expensive facilities costs.
Shell protection device
Shell is made of stainless steel or aluminum alloy.Protection grade can reach IP20 and IP23.IP20 housing can prevent solid foreign objects of diameter more than 12mm enter into and protect the transformer safely.IP23 housing can prevent the vertical drop of less than 60°of flow,suits for outdoor operation.

Note:IP23 housing can make the transformer cool,small capacity is decreased by about 5%,high-capacity is decreased by about 10%.
Temperature control and temperature display

Temperature control system is composed of temperaturecontroller and PTC thermometerelement of lower voltage winding in the hottest point.Realize tocontrol and measure thetemperature of transformer.lfthe operationis failure for overload or transformer winding temperature is too high,the temperature controler will send an alarmingsignal.When the temperatureexceeds the value of their own safety trip.Forced air coolingby the temperature controler is accordingto the winding temperaturewhich is decided by input or switch coolingfan.
Direct indicationof temperaturedisplay system during the operationof the transformerwinding hot spot temperature,and temperature controlsystem can be used in conjunction.
Temperature control and temperature display system canbe installed in a certaindistance away fromthe main transformer,thelength of temperature component is:
Temperature control:<20m
Temperature display:<10m(2wires) <100m(2 wires with a compensating conductor)
Technical parameters
Type 12 of 6kV,10kV dry-type no-excitation distribution transformers Technical Date Sheet
额定容量 Rated Capacity (kVA) | 电压组合及分接范围 Voltage combination | 联结组标号 Connection group symbol | 空载损耗 No-load loss | 不同绝缘耐热等级下的负载损耗 Under the different insulayion heat- resisting rank load loss(W) | 空载电流 No-load current % | 短路阻抗 Short- circuit mpedance% | ||||
高压(H.V.) kV | 高压分接范围 High pressure tapping range% | 低压(L.V.) kV | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dynll | 150 | 670 | 710 | 760 | 2.4 | 4.0 |
50 | 215 | 940 | 1000 | 1070 | 2.4 | |||||
80 | 295 | 1290 | 1380 | 1480 | 1.8 | |||||
100 | 320 | 1480 | 1570 | 1690 | 1.8 | |||||
125 | 375 | 1740 | 1850 | 1980 | 1.6 | |||||
160 | 430 | 2000 | 2130 | 2280 | 1.6 | |||||
200 | 495 | 2370 | 2530 | 2710 | 1.4 | |||||
250 | 575 | 2590 | 2760 | 2960 | 1.4 | |||||
315 | 705 | 3270 | 3470 | 3730 | 1.2 | |||||
400 | 785 | 3750 | 3990 | 4280 | 1.2 | |||||
500 | 930 | 4590 | 4880 | 5230 | 1.0 | |||||
630 | 1070 | 5530 | 5880 | 6290 | 1.0 | |||||
630 | 1040 | 5610 | 5960 | 6400 | 1.0 | 6.0 | ||||
800 | 1215 | 6550 | 6960 | 7460 | 1.0 | |||||
1000 | 1415 | 7650 | 8130 | 8760 | 1.0 | |||||
1250 | 1670 | 9100 | 9690 | 10370 | 1.0 | |||||
1600 | 1960 | 11050 | 11730 | 12580 | 1.0 | |||||
2000 | 2440 | 13600 | 14450 | 15560 | 0.8 | |||||
2500 | 2880 | 16150 | 17170 | 18450 | 0.8 | |||||
Type 14 of 6kV,10kV dry-type no-excitation distribution transformers Technical Date Sheet
额定容量 Rated Capacity (kVA) | 电压组合及分接范围 Voltage combination | 联结组标号 Connection group symbol | 空载损耗 No-load loss W | 不同绝缘耐热等级下的负载损耗 Under the different insulayion heat- resisting rank load loss(W) | 空载电流 No-load current % | 短路阻抗 Short- circuit impedance% | ||||
高压(H.V.) kV | 高压分接范围 High pressure tapping range% | 低压(LV.) kV | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dynll | 130 | 605 | 640 | 685 | 2.4 | 4.0 |
50 | 185 | 845 | 900 | 965 | 2.4 | |||||
80 | 250 | 1160 | 1240 | 1330 | 1.8 | |||||
100 | 270 | 1330 | 1415 | 1520 | 1.8 | |||||
125 | 320 | 1565 | 1665 | 1780 | 1.6 | |||||
160 | 365 | 1800 | 1915 | 2050 | 1.6 | |||||
200 | 420 | 2135 | 2275 | 2440 | 1.4 | |||||
250 | 490 | 2330 | 1485 | 2665 | 1.4 | |||||
315 | 600 | 2945 | 3125 | 3355 | 1.2 | |||||
400 | 665 | 3375 | 3590 | 3850 | 1.2 | |||||
500 | 790 | 4130 | 4390 | 4705 | 1.0 | |||||
630 | 910 | 4975 | 5290 | 5660 | 1.0 | |||||
630 | 885 | 5050 | 5365 | 5760 | 1.0 | 6.0 | ||||
800 | 1035 | 5895 | 6265 | 6715 | 1.0 | |||||
1000 | 1205 | 6885 | 7315 | 7885 | 1.0 | |||||
1250 | 1420 | 8790 | 8720 | 9335 | 1.0 | |||||
1600 | 1665 | 9945 | 10555 | 11320 | 1.0 | |||||
2000 | 2075 | 12240 | 13005 | 14005 | 0.8 | |||||
2500 | 2450 | 14535 | 15445 | 16605 | 0.8 | |||||
Type 18 of 6kV,10kV dry-type no-excitation distribution transformers Technical Date Sheet
额定容量 Rated Capacity (kVA) | 电压组合及分接范围 Voltage combination | 联结组标号 Connection group symbol | 空载损耗 No-load loss W | 不同绝缘耐热等级下的负载损耗 Under the different insulayion heat- resisting rank load loss(W) | 空载电流 No-load current % | 短路阻抗 Short- circuit mpedance% | ||||
高压(H.V.) kV | 高压分接范围 High pressure tapping range% | 低压(L.V.) kV | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dynl1 | 105 | 605 | 640 | 685 | 2.4 | 4.0 |
50 | 155 | 845 | 900 | 965 | 2.4 | |||||
80 | 210 | 1160 | 1240 | 1330 | 1.8 | |||||
100 | 230 | 1330 | 1415 | 1520 | 1.8 | |||||
125 | 270 | 1565 | 1665 | 1780 | 1.6 | |||||
160 | 310 | 1800 | 1915 | 2050 | 1.6 | |||||
200 | 360 | 2135 | 2275 | 2440 | 1.4 | |||||
250 | 415 | 2330 | 1485 | 2665 | 1.4 | |||||
315 | 510 | 2945 | 3125 | 3355 | 1.2 | |||||
400 | 570 | 3375 | 3590 | 3850 | 1.2 | |||||
500 | 670 | 4130 | 4390 | 4705 | 1.0 | |||||
630 | 775 | 4975 | 5290 | 5660 | 1.0 | |||||
630 | 750 | 5050 | 5365 | 5760 | 1.0 | 6.0 | ||||
800 | 875 | 5895 | 6265 | 6715 | 1.0 | |||||
1000 | 1020 | 6885 | 7315 | 7885 | 1.0 | |||||
1250 | 1205 | 8790 | 8720 | 9335 | 1.0 | |||||
1600 | 1415 | 9945 | 10555 | 11320 | 1.0 | |||||
2000 | 1760 | 12240 | 13005 | 14005 | 0.8 | |||||
2500 | 2080 | 14535 | 15445 | 16605 | 0.8 | |||||
Type 10 of 6kV,10kV dry-type no-excitation distribution transformers Technical Date Sheet
额定容量 Rated Capacity (kVA) | 电压组合及分接范围 Voltage combination | 联结组标号 Connection group symbol | 空载损耗 No-load loss (I) | 不同绝缘耐热等级下的负载损耗 Under the different insulayion heat- resisting rank load loss(W) | 空载电流 No-load current % | 短路阻抗 Short- circuit impedance% | ||||
高压(H.V.) (kV) | 高压分接范围 High pressure tapping ranges | 低压(L.V.) (kV) | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dynl1 | 190 | 670 | 710 | 760 | 2.0 | 4.0 |
50 | 270 | 940 | 1000 | 1070 | 2.0 | |||||
80 | 370 | 1290 | 1380 | 1480 | 1.5 | |||||
100 | 400 | 1480 | 1570 | 1690 | 1.5 | |||||
125 | 470 | 1740 | 1850 | 1980 | 1.5 | |||||
160 | 540 | 2000 | 2130 | 2280 | 1.3 | |||||
200 | 620 | 2370 | 2530 | 2710 | 1.3 | |||||
250 | 720 | 2590 | 2760 | 2960 | 1.1 | |||||
315 | 880 | 3270 | 3470 | 3730 | 1.1 | |||||
400 | 980 | 3750 | 3990 | 4280 | 1.0 | |||||
500 | 1160 | 4590 | 4880 | 5230 | 1.0 | |||||
630 | 1340 | 5530 | 5880 | 6290 | 0.85 | |||||
630 | 1300 | 5610 | 5960 | 6400 | 0.85 | 6.0 | ||||
800 | 1520 | 6550 | 6960 | 7460 | 0.85 | |||||
1000 | 1770 | 7650 | 8130 | 8760 | 0.85 | |||||
1250 | 2090 | 9100 | 9690 | 10300 | 0.85 | |||||
1600 | 2450 | 11000 | 11700 | 12500 | 0.85 | |||||
2000 | 3050 | 13600 | 14400 | 15500 | 0.7 | |||||
2500 | 3600 | 16100 | 17100 | 18400 | 0.7 | |||||
1600 | 2450 | 12200 | 12900 | 13900 | 0.85 | 8.0 | ||||
2000 | 3050 | 15000 | 15900 | 17100 | 0.7 | |||||
2500 | 3600 | 17700 | 18800 | 20200 | 0.7 | |||||
Type 11 of 6kV,10kV dry-type no-excitation distribution transformers Technical Date Sheet
额定容量 Rated Capacity (kVA) | 电压组合及分接范围 Voltage combination | 联结组标号 Connection group symbol | 空载损耗 No-load loss (W) | 不同绝缘耐热等级下的负载损耗 Under the different insulayion heat- resisting rank load loss(W) | 空载电流 No-load current % | 短路阻抗 Short- circuit impedance | ||||
高压(H.V.) (kV) | 高压分接范围 H动pressur tapping ranges | 低压(LV.) (kV) | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dynl1 | 170 | 670 | 710 | 760 | 1.9 | 4.0 |
50 | 240 | 940 | 1000 | 1070 | 1.9 | |||||
80 | 330 | 1290 | 1380 | 1480 | 1.5 | |||||
100 | 360 | 1480 | 1570 | 1690 | .5 | |||||
125 | 420 | 1740 | 1850 | 1980 | 1.3 | |||||
160 | 480 | 2000 | 2130 | 2280 | 1.3 | |||||
200 | 550 | 2370 | 2530 | 2710 | 1.1 | |||||
250 | 640 | 2590 | 2760 | 2960 | 1.1 | |||||
315 | 790 | 3270 | 3470 | 3730 | 1.0 | |||||
400 | 880 | 3750 | 3990 | 4280 | 1.0 | |||||
500 | 1040 | 4590 | 4880 | 5230 | 0.9 | |||||
630 | 1200 | 5530 | 5880 | 6290 | 0.9 | |||||
630 | 1170 | 5610 | 5960 | 6400 | 0.9 | 6.0 | ||||
800 | 1360 | 6550 | 6960 | 7460 | 0.8 | |||||
1000 | 1590 | 7650 | 8130 | 8760 | 0.8 | |||||
1250 | 1880 | 9100 | 9690 | 10370 | 0.8 | |||||
1600 | 2200 | 11000 | 11700 | 12500 | 0.7 | |||||
2000 | 2740 | 13600 | 14400 | 15500 | 0.6 | |||||
2500 | 3240 | 16100 | 17100 | 18400 | 0.6 | |||||
1600 | 2200 | 12200 | 12900 | 13900 | 0.7 | 8.0 | ||||
2000 | 2740 | 15000 | 15900 | 17100 | 0.6 | |||||
2500 | 3240 | 17700 | 18800 | 20200 | 0.6 | |||||
Type 13 of 6kV,10kV dry-type no-excitation distribution transformers Technical Date Sheet
额定容量 Rated Capacity (kVA) | 电压组合及分接范围 Voltage combination | 联结组标号 Connection group symbol | 空载损耗 No-load loss W | 不同绝缘耐热等级下的负载损耗 Under the different insulayion heat- resisting rank load loss(W) | 空载电流 No-load current | 短路阻抗 Short- circuit impedance% | ||||
高压(H.V.) kV | 高压分接范围 High pressure tapping ranges | 低压(L.V.) kV | 130℃(B) (100℃) | 155℃(F) (120℃) | 180℃(H) (145℃) | |||||
30 | 6~11 | ±2×2.5 | 0.4 | Yyn0 Dynl1 | 135 | 605 | 640 | 685 | 2.4 | 4.0 |
50 | 195 | 845 | 900 | 965 | 2.4 | |||||
80 | 265 | 1160 | 1240 | 1330 | 1.8 | |||||
100 | 290 | 1330 | 1410 | 1520 | 1.8 | |||||
125 | 340 | 1560 | 1660 | 1780 | 1.6 | |||||
160 | 385 | 1800 | 1910 | 2050 | 1.6 | |||||
200 | 445 | 2130 | 2270 | 2440 | 1.4 | |||||
250 | 515 | 2330 | 2480 | 2660 | 1.4 | |||||
315 | 635 | 2940 | 3120 | 3350 | 1.2 | |||||
400 | 705 | 3370 | 3590 | 3850 | 1.2 | |||||
500 | 835 | 4130 | 4390 | 4700 | 1.0 | |||||
630 | 965 | 4970 | 5290 | 5660 | 1.0 | |||||
630 | 935 | 5050 | 5360 | 5760 | 1.0 | 6.0 | ||||
800 | 1090 | 5890 | 6260 | 6710 | 1.0 | |||||
1000 | 1270 | 6880 | 7310 | 7880 | 1.0 | |||||
1250 | 1500 | 8190 | 8720 | 9330 | 1.0 | |||||
1600 | 1760 | 9940 | 10500 | 11300 | 1.0 | |||||
2000 | 2190 | 12200 | 13000 | 14000 | 0.8 | |||||
2500 | 2590 | 14500 | 15400 | 16600 | 0.8 | |||||
1600 | 1760 | 11000 | 11600 | 12500 | 1.0 | 8.0 | ||||
2000 | 2190 | 13500 | 14300 | 15400 | 0.8 | |||||
2500 | 2590 | 15900 | 17000 | 18200 | 0.8 | |||||