66kV~110kV  oil-immersed  powertransformers

66kV~110kV oil-immersed powertransformers

66kV~110kV oil-immersed powertransformers
Description

Product Structure and Process Characteristics

The oil-immersed power transformers produced by our company are based on the advanced technologies at  home and abroad,and are designed independently according to the characteristics of Chinese urban and rural power  grid.Our  product  performance is better than the GB/T6451 Three-phase Oil-type  Power  Transformer  Technical  Parameters and Requirements,in fullcompliance with JB/T3837 Transformer Product Model Preparation Method,the manufacturing standards of GB/T1094 Power Transformers and the IEC standards recommended by the International  Electrotechnical Commission and GB20052-2020"power transformer limited value of energy efficiency and energy efficiency  level".

The  product  is characterized by low loss,low  noise,anti-leakage and  no suspension core.It  has extraordinary innovation in safety,reliability,economic efficiency and other aspects,so thatit becomes a first-class technical product  in China.The product has the following characteristics:

Iron  Core  of  Transformer:Its iron core  adopts  multi-step  stepping  lap-type  technology,the  laminated  piece  adopts 45°oblique seam hole-free bandage structure,silicon steel sheet adopts advanced longitudinal and horizontal  shear cutting,cutting mouth burr is not more than 0.02 mm.In addition,the advanced iron core stacking station,strict stacking  and  no  pre-stack  yoke  process  fully  guarantee  the  grain  orientation  of  silicon   steel  sheet,effectively  reducing  the no-load loss of the transformer.The iron core adopts high-strength PET polyester banding design,clip structure  adopts  plate  clamp  pieces,thus  reducing  spurious  loss.The  iron yoke  clamper adopts a  unique  clamping  banding  process,fully guarantees the  iron core's clamping degree.At the same time,over years of development,the  mature  technology makes iron core,pull plate,roof beam,side beam and pad become a fim organic whole,and ensures that  their on core sheet is in the best state to resist pressure,thereby reducing the transformer's no-load loss and greatly  lowering the noise of transformer.

Transformer  Winding:The  transformer's   high,medium,low  and  voltage-regulating  coil  shall  wound  on an   insulating  paper tube.Low-voltage winding  mainly adopts spiral structure with axial oil  passage.High and  medium  voltage windings are made by composite wire wrapped by high-strength Dennison paper,which is imported from the United  States,they  can  greatly  increasethe  filing  coefficient  of  transformer's  steel  window,reduce  the  wire's  eddy current loss and circulation loss,and also improve the anti-short circuit capacity of the transformer.There are locking stays (namely reinforced stayslinside and outside the winding.The winding's radial fastening adopts the design of0  margin,which greatly enhances the winding's mechanical strength and short circuit resistance.Meanwhile,the high,   medium and low-voltage windingshall equipped with an oil-oriented structure,which reduces the temperature rise at  the hottest points of winding,thus extending the transformer's service life.The on-load tap changing transformer has  an  independent  voltage-regulating  winding,so  that  the  winding's  ampere  turns  are  more  balanced,the  stability  is  improved,and the instability and deformation are eliminated,thus effectively reducing the transformer's axial power        caused by external short-circuit,and improving the transformer's dynamic stabilityin the case of external fault.

Transformer Body Insulation:The transformer's body insulation structure and winding process are completed in a fully sealed clean workshop,can meet the cleanliness requirements and constant body temperature requirements for high  voltage,ultra-high  voltage  transformers,and  further  ensure  the  cleanliness  and  dryness  of  transformer  body.        Meanwhile,kerosene vapor-phase drying equipment is used to further ensure the cleanliness of the body.The lower pallet and upper pressure plate of the body all dopt electricallaminated wood with high mechanical strength and good electrical performance.The stays and pads in the transformer all have gone through high-precision cutting and rounding  processes,greatly reducing the partial discharge.The steel clamp and steel nails have sufficient strength,the pressure  contact  surface that  connects  pressure  sheet  is  designed  to  be  the  maximum.Support  pads,stays  and  nails  are arranged ina way to make the winding has balanced pressure,and enhance the overallstability.The body adopts overall  package constant-pressure drying process,shortens the assembly time after winding is stabilized.The winding con-  centricity is adjusted,so that the cores will be consistent as much as possible,fully ensure that the coils have equal  reactance height,keep even pressure on the winding,thereby improving each winding's anti-short circuit capability,  In addition,the lower clamp and lower fuel tank adopt a four-week steel positioning,and can be adjusted or locked  through anti-pressure nails;upper beam and upper fuel tank lid adopt epoxy resin curing positioning,so the body can  withstand the impact of variety of transport conditions in the tank,and does not shift when there is axial electric power  in the operation.

Transformer Lead Wire:The transformer's high and medium-voltage tap wires are fixed by a bracketand led to the switch,low-voltage lead copper wire is fixed onto the upper and lower clamps to improve the stability of lead wire.  Besides,the coil binding standards and technological process greatly reduce the transformer's partial discharge.

Transformer Tank:Large and medium transformers adopt bell-type fuel tank structure.Large-scale folding  machine is used for corrugated molding.Various reinforced iron sheets and reinforced boards are cancelled.This not  only greatly improves the mechanical strength of oil tank,but also reduces the leakage caused by welding,increases  the effective cooling surface of the body,and improves the cooling effect.Meanwhile,due to the divergent effect of  corrugated box wall,the noise of transformer is effectively reduced.The seal part of tank is treated with special pro-  cessing,and the whole fuel tank adopts"shot peening'treatment,thus completely removing the oxidized surface of the  box,as well as the sharp corners and welding slag caused by the processing,improving the adhesion of paint,and  making the transformer more beautiful and durable.Radiator and other components are tested and inspected by simu-   lating the field operation in harsh environmental conditions,thus effectively removing the leakage point.All the flange  surfaces are refined,and set slotted position limiting structure.A high-quality oil-resistant,ozone-resistant acrylic  rubber gasket is adoptedto prevent the leakage of thetransformer.In addition,the transformer's upper and lower fuel  tanks can be connected by bolts,and can also adopt seal structure along the upper and lower fuel tanks according to  the  user's  requirements.

Transformer Cooling and Accessories:It generally adopts air-cooled/self-cooled type,and has full-load opera-  tion when the fan starts,andbegins naturally cooling when the fanstops,the load is 67%of fulload.Chip radiatorshall arranged in a reasonable and compact way,fans are generally hung over radiators,blowing in horizontal or vertical  direction.The oil storage tank is generally capsule type,which has an oil-resistant,airtight capsule.It completely  isolates from the oil of transformer from the air,and achieves full sealing.In addition,it can also adopt the expansion  metal corrugated oil storage cabinet (internal oil cabinet or external oil cabinet)made by stainless steel.It is mainte-  nance-free,and has reliable operation.

With advanced technologies,the Company has implemented perfect quality assurance system,adopted reliable  product structure design and advanced technological processes,and ensured that our products have high reliability,low  partial discharge,low loss and low noise.

Technical parameters and characteristics

Technical specification

1.Voltage  rating:66KV~110kV;


2.Voltage regulating   method:on-load voltage regulating,no-load voltage regulating;

3.Rated capacity:630  63000kVA(see the attached sheet,it can be customized according tousers'requirements): 

4.Frequency:50Hz;

5.Number of phases:3-phase;

6.Label of connection group:according to national standards orusers'requirements;                       

7.Short circuit impedance:according to national standards orusers'requirements;                           

8.Application environment:according tonational standards or users'requirements;

9.Cooling method:oil-immersed  self-cooling,air-cooled

Application environment and conditions

1.Device type:outdoor type

2.Ambient temperature:the  maximum temperature+40,the  minimum  temperature-30

3.Altitude:≤1000 m(The temperature rise should be modified if the altitude is higher than 1000 m) 

4.Relative    humidity:≤90%(25)

5.Installation site:places with no corrosive gas and no obvious dirt

Product  model  description

Protection code(generally isnot marked,TH--hot and humid,TA-dry heat) 

High voltage level (kV)

Rated capacity(kVA)

Performance level code(11,or according to user's requirements)

Z:On-load distribution;no-excitation distribution is not marked

S:Three-winding;two-winding  is  not  marked

F:air-cooled;self-cooledis  not  marked

Three-phase

Notes for Customers

Please provide the following parameters when placing an order:

1.Product  modelo

2.Rated  capacityo

3.Voltage  combination  C

4.Voltage  regulation  range

5.Frequency           

6.Label of connection group

7.Short circuit impedance

8.Other:special requirements should be noted.


Product performance parameters

66KV three-phase two-winding no-excitation distribution transformer




额定容量

Rated

Capacity

(kVA)


1级(S22型)


2级(S20型)


3级(S13型)


短路阻抗

Short-

circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


3150


2.2


20.7


2.6


20.7


3.2


21.9



8


4000


2.6


24.6


3.1


24.6


3.8


25.9


5000


3.1


27.6


3.7


27.6


4.6


29.2


6300


4.0


30.8


4.7


30.8


5.8


32.5








9


8000


4.9


36.5


5.8


36.5


7.1


38.5


10000


5.8


43.0


6.8


43.0


8.4


45.4


12500


6.8


51.1


8.7


51.1


9.9


54.0


16000


8.3


62.8


9.8


62.8


12.0


66.3


20000


9.7


76.1


11.4


76.1


14.1


80.4


25000


11.4


90.0


13.5


90.0


16.6


95.0


31500


13.5


108.0


16.0


108.0


19.7


114.0


40000


16.5


126.9


19.1


126.9


23.5


134.0


50000


19.4


150.3


22.9


150.3


28.2


158.7


63000


22.9


178.2


27.0


178.2


33.3


188.1

66KV three-phase two-winding on-load voltage regulating power transformer


额定容量

Rated

Capacity

(kVA)


1级(S22型)


2级(S20型)


3级(S13型)


短路阻抗

Short-

circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


6300


4.4


30.8


5.2


30.8


6.4


32.5








9


8000


5.3


36.5


6.2


36.5


7.7


38.5


10000


6.2


43.0


7.3


43.0


9.0


45.4


12500


7.4


51.1


8.7


51.1


10.7


54.0


16000


8.9


62.8


10.5


62.8


12.9


66.3


20000


10.6


76.1


12.5


76.1


15.4


80.4


25000


12.5


90.0


14.8


90.0


18.2


95.0


31500


14.8


108.0


17.5


108.0


21.5


114.0


40000


17.7


126.9


20.9


126.9


25.8


134.0


50000


20.9


150.3


24.7


150.3


30.4


158.7


63000


24.7


178.2


29.2


178.2


35.9


188.1

Type 11 of 66kV three-phase two-winding no-excitation distribution transformer


额定容量

Rated

Capacity

(kVA)


电压组合及分接范围

Voltage combination(kV)


联结组标号    Connection

group symbol



空载损耗

No-load loss

(W)



负载损耗

Load loss

(W)


空载电流     No-load    current

%


短路阻抗

Short-

circuit

impedance%


高压(H.V.)

(kV)


高压分接范围  High pressure   tapping range%


低压(L.V.)


(kV)


630





63

66

69






±5




6.3

6.6

10.5





Yd11


1200


7100


1.1






8.0


800


1500


8500


1.0


1000


1700


9800


1.0


1250


2000


11900


1.0


1600


2400


14000


1.0


2000


2800


16600


0.96


2500


3400


19600


0.88


3150






YNd11


4000


23000


0.84


4000


4800


27300


0.80


5000


5700


30700


0.68


6300





63

66




±2×2.5




6.3

6.6

10.5


7300


34200


0.60






9.0


8000


8900


40500


0.60


10000


10500


47800


0.56


12500


12400


56800


0.56


16000


15000


69800


0.52


20000


17600


84600


0.52


25000


20800


100000


0.48


31500


24600


120000


0.44


40000


29400


141000


0.44


50000


35200


167000


0.40


63000


41600


198000


0.36

Note 1:When the number of taps and stage voltage remain unchanged,it is allowed to increase the number of  negative taps while reducing the number of positive taps,or increase the number of positive tapswhile reducing the number of negative taps,such as.

Type 11of 66kV three-phase two-winding on-load tap changing transformer



额定容量

Rated

Capacity


(kVA)



电压组合及分接范围

Voltage combination(kV)



联结组标号    Connection

group symbol



空载损耗

No-loadloss

(W)


负载损耗

Loadloss

(W)


空载电流     No-load    current

%



短路阻抗

Short-

circuit

impedance%


高压(H.V.)

(kV)


高压分接范围  High pressure  tapping range%


低压(L.V.)

(kV)


6300


的明的




±8×1.25





6.3

6.6

10.5





YNd11


8000


34200


0.60




9.0~11.0


8000


9600


40500


0.60


10000


11300


47800


0.56


12500


13400


56800


0.56


16000


16100


69800


0.52


20000


19200


84600


0.52


25000


22700


100000


0.48


31500


26900


120000


0.44


40000


32200


141000


0.44


50000


38000


167000


0.40


10.0~12.0


63000


44900


198000


0.36


110kV three-phase two-winding on-excitation distribution transformer


额定容量

Rated

Capacity

(kVA)





短路阻抗

Short-

circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


6300


4.1


32


4.8


32


5.9


33









10.5


8000


4.9


38


5.8


38


7.1


40


10000


5.8


45


6.8


45


8.4


48


12500


6.8


53


8.7


53


9.9


56


16000


8.3


65.7


9.8


65.7


12.0


69


20000


9.7


79


11.4


79


14.1


84


25000


11.4


94


13.5


94


16.6


99


31500


13.5


111


16.0


111


19.7


117


40000


16.2


133


19.1


133


23.5


141


50000


19.4


158


22.9


158


28.2


166


63000


22.9


187


27.0


187


33.3


198


75000


26.0


212


30.7


212


37.8


224




12~14


90000


29.9


245


35.4


245


43.5


258


120000


37.3


303


44.1


303


54.2


320


150000


44.1


359


52.1


359


64.1


379


180000


49.5


411


58.5


411


72.0


434

110kV three-phase two-winding on-load tap changing transformer



额定容量

Rated

Capacity

(kVA)


1级(S22型)


2级(S20型)


3级(S13型)



短路阻抗

Short-

circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


6300


4.4


32


5.2


32


6.4


33









10.5


8000


5.3


38


6.2


38


7.7


40


10000


6.2


45


7.3


45


9.0


48


12500


7.4


53


8.7


53


10.7


56


16000


8.9


66


10.5


66


12.9


69


20000


10.6


79


12.5


79


15.4


84


25000


12.5


94


14.8


94


18.2


99


31500


14.9


111


17.6


111


21.6


117


40000


17.8


140


21.0


140


25.8


148


50000


21.0


175


24.8


175


30.6


184


63000


25.0


209


29.5


209


36.3


220

110kV three-phase three-winding no-excitation distribution transformer



额定容量

Rated

Capacity

(kVA)


1级(S22型)


2级(S20型)


3级(S13型)


短路阻抗

Short-circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)



升压


降压


6300


4.9


40


5.8


40


7.1


42





高一中

17.5~18.5

高一低

10.5

中一低6.5






高一中10.5

高一低

17.5~18.5

低6 . 5


8000


5.8


48


6.9


48


8.5


50


10000


6.9


56


8.2


56


10.1


59


12500


8.1


67


9.6


67


11.8


70


16000


9.8


81


11.6


81


14.3


86


20000


11.6


95


13.7


95


16.9


101


25000


13.5


113


16.0


113


19.7


120


31500


16.2


134


19.1


134


23.5


142


40000


19.1


161


22.6


161


27.8


170


50000


22.9


192


27.0


192


33.3


202


63000


27.1


230


32.0


230


39.4


243

110kV three-phase three-winding on-load tap changing transformer


额定容量

Rated

Capacity

(kVA)





短路阻抗

Short-

circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


6300


5.3


40


6.2


40


7.7


42







高—中


10.5


8000


6.3


48


7.5


48


9.2


50


10000


7.5


56


8.8


56


10.9


59


12500


8.9


67


10.5


67


12.9


70


16000


10.6


81


12.5


81


15.4


86









20000


12.5


95


14.8


95


18.2


101


高—低


17.5~18.5 中一低6.5


25000


14.9


113


17.6


113


21.6


120


31500


17.7


134


20.9


134


25.7


142


40000


21.2


161


25.0


161


30.8


170


50000


25.0


192


29.6


192


36.4


202


63000


29.8


230


35.2


230


43.3


243

110kV low-voltage 35kV three-phase two-winding no-excitation distribution transformer



额定容量

Rated

Capacity

(kVA)


1级(S22型)


2级(S20型)


3级(S13型)



短路阻抗

Short-

circuit

impedance%


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)



空载损耗

No-load loss

(kW)


负载损耗

Load loss

(75℃)

(kW)


6300


4.4


33


5.2


33


6.4


35









10.5


8000


5.3


40


6.2


40


7.7


42


10000


6.2


47


7.3


47


9.0


49


12500


7.2


56


8.5


56


10.5


59


16000


8.6


68


10.1


68


12.5


72


20000


10.2


85


12.0


85


14.8


89


25000


12.1


99


14.2


99


17.5


105


31500


14.3


120


16.8


120


20.7


126


40000


16.9


140


20.0


140


24.6


147


50000


20.3


174


24.0


174


29.5


183


63000


24.0


209


28.3


209


34.9


220

Type 11 of 110kV three-phase two-winding no-excitation distribution transformer


额定容量

Rated

Capacity

(kVA)



电压组合及分接范围

Voltage combination(kV)



联结组标号


Connection    group symbo



空载损耗

No-load loss

(W)



负载损耗

Load loss

(W)



空载电流     No-load    current

%


短路阻抗

Short-

circuit

impedance%


高压(H.V.)

(kV)


高压分接范围  High pressure tapping range%



低压(L.V.)

(kV)


6300









110

115

121










±2×2.5






6.3

6.6

10.5











YNd11


7400


35000


0.62








10.5


8000


8900


42000


0.62


10000


10500


50000


0.58


12500


12400


59000


0.58


16000


15000


73000


0.54


20000


17600


88000


0.54


25000


20800


104000


0.50


31500


24600


123000


0.48


40000


29400


148000


0.45


50000


35200


175000


0.42


63000


41600


208000


0.38


75000


13.8

15.75

18

21


47200


236000


0.33




12.0~14.0


90000


54400


272000


0.30


120000


67800


337000


0.27


150000


80100


399000


0.24


180000


90000


457000


0.20

Type 11 of 110kV three-phase three-winding no-excitation distribution transformer


额定容量

Rated

Capacity

(kVA)


电压组合及分接范围

Voltage combination(kV)



联结组标号  Connection  group symbol



空载损耗

No-load loss

(W)



负载损耗

Load loss

W



空载电流     No-load     current

%


短路阻抗

Short-circuit impedance%


高压(H.V.)

(kV)


高压分接范围 High   pressure tapping range%


中压(M.V.) (kV)


低压(L.V.)

(kV)



升压


降压


6300





10

15

21







±2×2.5



5





6.3

6.6

25






YNyn0d11


8900


44000


0.66





高-中

17.5~18.5

高-低

10.5

中-低

6.5





高-中

10.5

高-低

18~19

中-低

6.5


8000


10600


53000


0.62


10000


12600


62000


0.59


12500


14700


74000


0.56


16000


17900


90000


0.53


20000


21100


106000


0.48


25000


24600


126000


0.48


31500


29400


149000


0.48


40000


34800


179000


0.44


50000


41600


213000


0.44


63000


49200


256000


0.40

Note  1:The capacity ratio of high,medium and low-voltage capacity is(100/100/100)%respectively. 

Note 2:According to the requirements,the label of connection group is YNynOd11.

Note  3:According  to  users'requirements,the  medium-voltage  transformer  can  adopt  the  voltage  value  that  is different from the table or set taps.

Note 4:Step-up transformer should adopt tap-free structure.Taps can be usedif there are operationalrequirements.

Note 5:When the number of taps and stage voltage remain unchanged,it is allowed to increase the number of  negative taps while reducing the number of positive taps,or increase the number of positive tapswhile reducing the number of negative taps.

Note 6:Ifa user wants to buy a transformerwith a short circuit impedance value thatis different from the specified short circuit impedance value in the table,we should discuss the loss and other performance parameters,and specify  the  user's  requirement  in  the  contract.


Type 11 of 110kV three-phase two-winding on-load tap changing transformer



额定容量

Rated

Capacity

(kVA)


电压组合及分接范围

Voltage combination(kV)


联结组标号    Connection    group symbol


空载损耗

No-load loss

(W)



负载损耗

Load loss

W



空载电流     No-load    current

%


短路阻抗

Short-

circuit

impedance%


高压(H.V.)    kV


高压分接范围  High pressure tapping range%


低压(L.V.) kV


6300




110





±8×1.25



6.3

6.6

10.5

21





YNd11


8000


35000


0.64




10.5


8000


9600


42000


0.64


10000


11300


50000


0.59


12500


13400


59000


0.59


16000


16100


73000


0.55


20000


19200


88000


0.55


25000


22700


104000


0.51


31500


27000


123000


0.51


40000


32300


156000


0.46


12~18


50000


38200


194000


0.46


63000


45400


232000


0.42

Type 11 of 110kV three-phase three-winding on-load tap changing transformer


额定容量

Rated

Capacity

(kVA)


电压组合及分接范围

Voltage combination(kV)


联结组标号    Connection  group symbol



空载损耗

No-load loss

(W)



负载损耗

Load loss

W


空载电流     No-load     current

%


短路阻抗

Short-

circuit

impedance%


高压(H.V.) kV


高压分接范围 High pressure tapping range%


中压

(M.V.)

kV


低压(L.V.) kV


6300




110




±8×1.25





37

38.5



6.3

6.6

10.5

21





YNynOd11


9600


44000


0.76



高-中

10.5

高-低

18~19

中-低

6.5


8000


11500


53000


0.76


10000


13600


62000


0.71


12500


16100


74000


0.71


16000


19300


90000


0.67


20000


22800


106000


0.67


25000


27000


126000


0.62


31500


32100


149000


0.62


40000


38500


179000


0.58


50000


45500


213000


0.58





Note 1:The capacity ratio of high,medium and low-voltage capacity is(100/100/100)%respectively.                     

Note 2:According to the requirements,the label of connection group is YNynOd11.

Note 3:According to users'requirements,the medium-voltage transformer can adopt the voltage value that is different from the table or set taps.


Type 11 of 110KV low-voltage 35kV three-phase two-winding no-excitation distribution transformer


额定容量

Rated

Capacity

(kVA)


电压组合及分接范围

Voltage combination(kV)


联结组标号

Connection

group symbol



空载损耗

No-load loss

(W)



负载损耗

Load loss

W


空载电流     No-load    current

%


短路阻抗

Short-

circuit

impedance%


高压(H.V.)    kV


高压分接范围

High


pressure


低压(L.V.)    kV


6300






110

115

121






±2×2.5






36


38.5







YNd11


8000


37000


0.67






10.5


8000


9600


44000


0.67


10000


11200


52000


0.62


12500


13100


62000


0.62


16000


15600


76000


0.57


20000


18500


94000


0.57


25000


21900


110000


0.53


31500


25900


133000


0.53


40000


30800


155000


0.49


50000


36900


193000


0.49


63000


43600


232000


0.45

Note 1:Step-up transformer should adopt tap-free structure.Taps can be used if there are operational requirements

.Note 2:When the number of taps and stage voltage remain unchanged,it is allowed to increase the number of  negative taps while reducing the number of positive taps,or increase the number of positive taps while reducing the number of negative taps.

Note 3:If a user wants to buy a transformer with a short circuit impedance value that is different from the specified short circuit impedance value in the table,we should discuss the loss and other performance parameters,and specify  the user's requirement in the contract.

Note4:The transformers produced by the Company include but not limited to the above-listed products.If not  listed,we  can  reach  an  agreement  according  to  user's  requirements,and  then  design  and  manufacture  the 57 transformers  you  want.


About us
Sweep and follow our latest newsSweep and follow our latest news
Contact us
+251-996240434

Work Time:Monday to Friday 9:00-18:00

Contact:Mr TianFeng

Mobile:+86-139212208

Email:281858503@qq.com

Address:Room 302, Building 7, International(HeBi) Pioneer Park, HeBi City, HeNan Province,China

Bottom navigation
Addis ( Henan ) Science With Industry & Trading Co.,Ltd. was founded in 2024, with a registered capital of 5 million and over 40 employees. It is a professional electronic and electrical company. Excellent staff, advanced technology, excellent equipment and strict management are the basic of the continuous development of the company, the product can win the dependence of the user. "Reliable and professional" is our belief in the spirit of production and service.
On the basis of insisting on technological innovation, the company pays great attention to quality management, constantly improves the service level, realizes the good development of the democratic appraisal party members' summary of the company's business. We attentively participate in the promotion and the industry exchange activities. The company has excellent quality, good product performance and lead in the long-term development process. The technical advantages and many large factories in China have established long-term good partners. We also sincerely welcome customers from home and abroad to our company, visit and technical exchange!